pro-fi.gr

SAG COMPENSATOR

SAG COMPENSATOR

The VB-C series is an active voltage conditioner designed to solve voltage problems by SHIZUKI Smart Backup System. It responds instantly to power quality problems such as sags and swells, providing continuous regulation of voltage.

Key benefits

  • – Continuous protection from common utility voltage problems.
  • – Maintenance free.
  • – Faster return on investment thanks to high efficiency (98%).

Key features

  • – 3-level inverter technology with sophisticated control software.
  • – Scalable design.
  • – Colorful graphical touch screen interface.
  • – Eco-friendly: Non-use of Lead Acid Battery.
  • – Redundant internal bypass providing fail-safe operation.

Typical applications

  • Electronics industry
    Sensitive machinery, Clean room control
  • Food and beverage
    High speed bottling, Packaging lines
  • Continuous process
    Fiber production lines, Extrusion process
  • Automotive
    Welding process, Coating process, Painting process
  • – Pharmaceutical
    Batch process, Climate control

 

Technical Specification

Capacity 60kVA 120kVA 180kVA 240kVA 300kVA 360kVA
 

 

System

Phase 3 phase + N (4-wire)
Voltage 380V, 400V, 415V
Frequency 50 / 60 Hz
 

 

 

 

 

Input

 

 

Voltage (Operation Mode)

 

ECO Mode

380V system : 342V~418V 400V system : 360V~440V

415V system : 373.5V~456.5V

 

Dual Backup Mode

380V system : 200V~342V & 418V~480V

400V system : 200V~360V & 440V~480V

415V system : 200V~373.5V & 456.5V~480V

Backup Mode 200V~0V
Power factor Dual / Backup Mode ≧ 0.99
THDV Withstand ≦10%
 

 

 

 

 

 

 

Output

Phase 3 phase (3-, 4-wire)
Frequency  

Dual / Backup Mode

50/60Hz ±0.05%
Voltage 380V, 400V, 415V ±1% with linear load, ±3% with non-linear load
 

Correction Time (at full load)

15 minutes : 110% of system voltage ~ 480V input voltage 14 minutes : 90% remaining input voltage

10 minutes  : 70% remaining input voltage

10 seconds : 60% remaining input voltage ~ 200V input voltage

0.2 seconds : 200V ~ 0V input voltage

Response time ≦2ms
Applicable load power factor 0 ~ 1.0
Applicable load crest factor No limit (ECO Mode) / 3 : 1 (Dual / Backup Mode)
Overload current capability 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minutes
Storage device Aluminum Electrolytic capacitors (No battery)
 

Efficiency

ECO Mode > 98%
Dual / Backup Mode > 94%
 

 

Main Unit

Dimensions [mm] (W×D827×H1539) W=600 W=1200 W=1800 W=2400 W=3000 W=3600
Weight (kg) 230 460 690 920 1150 1380
Outline Drawing Fig.3、Fig.5
Distribution Board Unit (External

Bypass)

Parallels of Main Unit Up to 6 units
Dimensions [mm] (W×D×H) 400×827×1539
Outline Drawing Fig.4
 

 

Environment

Operation Temp. 0 ~ 40℃
Operation Humidity 0 ~ 95% (Without condensation)
Noise (at 1 meter) < 60dBA (ECO Mode)
 

 

 

 

Others

Tested to Standards LVD: EN62040-1, EMC requirements: EN62040-2
Compliance SEMI F47, IEC61000-4-11
Protection Grade IP20
Display and MMI 4.3″ colorful LCD touch screen
Built-in Comm. Port USB, EPO, Dry contact
Optional Comm. 2 Communication slots for SNMP card, RS-485 card, Dry contact card